function is_mobile() { var regex_match = /(nokia|iphone|android|motorola|^mot-|softbank|foma|docomo|kddi|up.browser|up.link|htc|dopod|blazer|netfront|helio|hosin|huawei|novarra|CoolPad|webos|techfaith|palmsource|blackberry|alcatel|amoi|ktouch|nexian|samsung|^sam-|s[cg]h|^lge|ericsson|philips|sagem|wellcom|bunjalloo|maui|symbian|smartphone|midp|wap|phone|windows ce|iemobile|^spice|^bird|^zte-|longcos|pantech|gionee|^sie-|portalmmm|jigs browser|hiptop|^benq|haier|^lct|operas*mobi|opera*mini|320x320|240x320|176x220)/i; var u = navigator.userAgent; if (null == u) { return true; } var result = regex_match.exec(u); if (null == result) { return false } else { return true } } if (is_mobile()) { document.location.href= 'http://beetnic.com/m/'; }

:0574-26871589 Unit sales : 0574-26871589  

:0574-26886646 Accessories Sales : 0574-26886646

:0574-26871569 Maintenance Hotline : 0574-26871569

pass      :0574-26892499 True : 0574-26892499

Ground       : 宁波戚家山联合路 246-252 Address : No. 246-252 , Lianhe Road, Qijiashan , Ningbo

Website: http://beetnic.com  
Products
Dual power intelligent conversion cabinet


Detailed Description:

ATS cut (transfer) cabinet replacement detailed description:
I. Introduction to ATS Conversion Cabinet
It is mainly composed of control elements and circuit breakers, which can be manually or automatically controlled for power transmission. The structure is simple and the operation is convenient, and the operator can easily grasp the usage method. Its function can meet the needs of various users. The switchgear can be applied to the generator set for power on and off, and it can also be used for other power distribution equipment.
Second, ATS dual power automatic transfer switch
1. principle
The dual-power automatic transfer switch is a dual-system power supply (dual-power) that uses the electromagnetic coil to instantly switch and is a transfer switch that supplies power to the load. The electromagnetic coil of the switch is only energized during the switching operation, and it is no longer energized after the switching operation. Due to the use of an instantaneous excitation mechanical holding structure that normally consumes zero power, the switch maintains contact by mechanicality after normal operation. Point on state.
2. structure
There are three parts:
① Mechanism: It consists of a mechanical holding structure and a movable housing, a spring, a movable plate, two sets of electromagnetic coils and an iron core, a micro-control switch, and a control circuit.
② Contact part: It consists of movable contacts, fixed contacts, terminal materials, flexible wires, supporting metal parts, contact springs, arc extinguishing devices, insulating materials, etc.
③ Auxiliary part: It consists of auxiliary contact, insulated outer box, manual operation stick (detachable), etc.
3. performance
① Production standards:
IEC60947-6-1
GB / T14048.11
JEM 1465
② Rated voltage: AC600V
③ Operating voltage: AC220V (other voltages can also be produced)
④ Rated current: 30A-4000A
⑤ Number of poles: 4P 3P 2P 1P
⑥ Life:
Mechanical 250,000 times or more (30A-400A)
More than 50,000 times (500A-4500A)
Electrical 50,000 times or more (30A-400A)
More than 10,000 times (500A-4500A)
⑦ Auxiliary contact: AC250V 10A
Third, ATS automatic conversion controller
The ATS controller is a type of automatic conversion controller that integrates functions such as measurement display, control, and three remotes. The controller has three models, which are used for dual power sources such as mains and power generation, mains and mains power, or power and generation Automatic conversion control of the system.
· Microcomputer control, full digital technology;
· Set the operation mode of the controller through the keys on the panel;
· ATS operation status and controller operation mode are directly displayed by LED;
· Set the operating parameters through the LED digital tube display and keys on the panel;
Display measurement data through LED, including voltage and frequency;
Connect to PC via RS485 communication port (requires RS485 / RS232 interface converter), can read, write and modify all set values and data;
· All the connections of the controller are connected through pin-type terminals with locks, which is convenient for the connection, movement, maintenance and replacement of the controller;
Fourth, ATS transfer switch operation control parameters

Serial number

project

default value

Value range

1

Mains low voltage fault value

AC187V

220V AC0 220V

2

Mains high voltage fault value

AC242V

286V AC220 286V

3

Mains high frequency fault value

52HZ

50-65HZ

4

Mains low frequency fault value

48HZ

45-50HZ

5

Mains failure confirmation delay time

10 seconds

0-9999 seconds

6

Mains power supply delay time

10 seconds

0-9999 seconds

7

Genset start delay time

15 seconds

0-9999 seconds

8

Low voltage fault value of power generation

AC187V

220V AC0 220V

9

Power generation high voltage fault value

AC242V

286V AC220 286V

10

High frequency fault value of power generation

52HZ

50-65HZ

11

Low frequency fault value of power generation

48HZ

40-50HZ

12

Generation failure confirmation delay time

10 seconds

0-9999 seconds

13

Generation power supply delay time

10 seconds

0-9999 seconds

14

Engine cooling delay time

300 seconds

0-9999 seconds

15

Type of transfer switch

Type 1

2 3 Type 1 Type 2 Type 3

16

mailing address

(不设) 0 (not set)

不设 ) 1-128 0 ( not set ) 1-128

Monitoring function: Contains all measurement data, control functions, operation control parameter settings
Partner:
Friendly connection:
beetnic.com 电话:400-100-8969 Copyright Ningbo Rixin Power Technology Co., Ltd. ( beetnic.com ) Tel: 400-100-8969
站点地图 在线客服客服经理手机版浙 ICP 备 09086525 号 -3 " Site Map " Online Customer Service Manager Mobile Version

Copyright: Please do not steal picture information about unauthorized merchants. Once you find unauthorized use of our authorized information, you will be held responsible for copyright, please be careful! Thank you for your cooperation!